10% DISCOUNT- info click stanga pe categoria ANALIZOARE PLC

- PLC ANALYZER, BLACK-BOX 2,        PROFIBUS, SIO-CHECK

prima paginaPRESIUNE - DETECTARE


pS76 Series Pressure Switch 15 to 1750 psi (1 to 121 bar) (cod: #271)
pS76 Series Pressure Switch  15 to 1750 psi (1 to 121 bar)
Specifications: 

 Wetted Parts 

Diaphragm: Kapton (polyimide)
Fitting: Zinc-Plated Steel (optional 316 SS)
O-Ring: Nitrile (other materials available)
 

Operating Temperature 

see table below 

Switch 

see table below

Electrical Termination  

DIN 43650A, IP65 Terminals 

Proof Pressure 

4500 psi (517 bar) except Range 10: 500 psi (35 bar) 

Burst Pressure  6000 psi (414 bar) 

Approvals 

CE, UL Approved units available, consult factory 

Weight, Approximate 

Steel: 0.6 lbs (0.27 kg) 

 

 

Recommended Operating Temperature Limits*

Diaphragm Material

-A, -B, -C Circuit without -RD

-AA, -BB, -CC Circuit or -RD

Teflon Coated Kapton®

-40°F to 185°F (-40°C to 85°C)

-40°F to 250°F (-40°C to 121°C)

 

Switch Ratings

Electrical Switch Ratings

AC

DC

-A, -B, -C without -G

5 amps @ 125/250 Volts

5 amps resistive, 3 amps inductive @28 Volts

-A, -B, -C with -G

1 amp @ 125 Volts

1 amp resistve, 0.5 amps inductive @ 28 Volts

-AA, -BB, -CC, without -G

2 switches rated 5 amps @ 125/250 Volts

2 switches rated 5 amps resistive, 3 amps inductive @ 28 Volts

-AA, -BB, -CC with -G

2 switches rated 1 amp @ 125/250 Volts

2 switches rated 1 amp resistive, 0.5 amps inductive @ 28 Volts

 

Repeatability / Deadband

 Pressure Range Code

Pressure Range 

Repeatability

Average Deadband*

-A, -B, -C Circuits 

10

15 - 75 psi (1-5.2 bar)

± 2.5 psi (0.17 bar) + 3% of setting

5 psig (0.34 bar) +11% of setting

20

50 - 150 psi (3.5-10 bar)

± 6 psi (0.41 bar) + 3% of setting 

15 psig (1.03 bar) + 14% of setting 

30

150 - 650 psi (10.3-44.8 bar)

± 15 psi (1.03 bar) + 3% of setting 

25 psi (1.72 bar) + 15% of setting 

40

500 - 1750 psi (34.5-121 bar)

±25 psi (17.2 bar) + 3% of setting

55 psi (3.79 bar) + 16% of setting 

-AA, -BB, -CC Circuits**

10

15 - 75 psi (1-5.2 bar) 

± 3.5 psi (0.24 bar) + 4% of setting

4 psig (0.28 bar) + 9% of setting 

20

50 - 150 psi (3.5-10.3 bar) 

± 9 psi (0.62 bar) + 4% of setting

13 psig (0.90 bar) + 11% of setting 

30

150 - 650 psi (10.3-44.8 bar) 

± 22 psi (1.51 bar) + 4% of setting

21 psi (17.2 bar) + 12% of setting 

40

500 - 1750 psi (34.5-121 bar)

± 35 psi (2.41 bar) + 4% of setting

45 psi (3.10 bar) + 13% of setting 

* In certain applications, deadband can be tailored and controlled to customer specifications. Consult factory for details.
** Operation of both switches in most cases will not be simultaneously, but will occur within the specifications listed. Deadband figures already reflect the improvement from the -RD option which is automatically included in the -AA, -BB, and -CC circuits.

Pret: Vă rugăm să ne contactaţi

Stoc disponibil: Intreaba


© Copyright 2012 btsautomation.ro | realizare site - rowebdesign.net